The vapour recovery system shall be protected
against flame transmission from one active fuelling nozzle to another active fuelling nozzle by at least one flame arrester. Vapour pumps certified including flame arresters may be accepted. 5.3.5.7 A flame arrester shall be positioned between any potential source of ignition in normal use of the metering pump/dispenser and the field connection point of the vapour pipe. |
||